          D Series High-Frequency Online UPS 1~3kVA

          Product profile

          Digital Series UPS adopts dual-conversion online design, intelligent MCU / DSP precision control; when mains is interrupted or restored, UPS transfer time is zero between main mode and battery mode, effectively ensuring the reliability of load operation.


          Basic Features

          Online-type design, zero transfer

          Digital Series UPS adopts dual-conversion online design, intelligent MCU / DSP precision control; when mains is interrupted or restored, UPS transfer time is zero between main mode and battery mode, effectively ensuring the reliability of load operation.

          High quality sine waves (THD<3%, linear) can be output either in mains mode or battery mode to provide the best power supply for the load.

          energy-efficient

          PFC power factor correction design and IGBT transformation technology are adopted, the input power factor is 0.99, and the overall efficiency is 90%.


          Detection and self-protection function

          Digital Series UPS can simulate the power failure and enter the battery mode. This function can be executed at any time through "self-test button" on the panel, or with random monitoring software; perfect self-protection function, peak current and short circuit protection design, super load impact resistance.


          TVSS function

          Namely, TRANSIENT VOLTAGE SURGE SUPPRESS burst wave voltage protection function. Utend FAX. TELEPHONE, MODEM network and other conversion protection.


          DC start function

          In the state of mains power failure, if UPS is needed to start the computer or other load equipment, Digital series UPS can be directly started in battery mode, making the use of UPS more convenient and reliable.


          Automatic bypass / manual bypass / maintenance bypass (optional)

          In addition to the automatic bypass function, the Digital series UPS also has the function of manually setting the bypass on the panel keys; when necessary, the manual maintenance bypass can also be optional for online maintenance.


          Optional lightning protection function

          Optional D class lightning protection device, with surge protection, lightning protection design, effectively protect the equipment from lightning interference.


          EPO emergency shutdown function (optional)

          Optional EPO switch to realize emergency shutdown of UPS.


          Rich and humanized LCD / LED content display

          UPS operating status (mains mode / battery mode / bypass mode), input and output, battery power, load size, and failure code, etc., at a glance.


          Extended time type power supply design

          Digital Series UPS fully provides extended time machines for users to choose from. The appropriate battery pack can bring the discharge time of the UPS to about 8 hours to meet the requirements of different power grid environments. Digital Series UPS extended time machine in addition to the discharge time to extend the battery recharge capacity is also very strong, can provide about 3 ~ 4A initial charging current (can also be selected according to user needs, a larger charging current).


          Can be used with a generator

          The ultra-wide input voltage and frequency range enable Digital series UPS to be used with mainstream brand generators to extend the use time and effectively remove the impure power generated by the generator, providing safe and stable power supply for the load.


          Adaptable perceptual load

          Digital Series UPS allows for sensitive load.


          Random monitoring software

          Rs 232 communication interface (optional USB interface), random monitoring software, to realize the intelligent management of UPS by users.


          Equipped with Intelligent Slot intelligent slot for remote monitoring (optional)

          Digital Series UPS is equipped with-Intelligent Slot smart slot, users can choose SNMP network card to realize centralized monitoring and remote monitoring and other functions.


          Technical Specifications


          Model

          D1K

          D1KS

          D2K

          D2KS

          D3K

          D3KS

          Rated capacity?

          (PF=0.9)

          1kVA/0.9kW

          2kVA/1.8kW

          3kVA/2.7kW

          Input

          Voltage

          120Vac~300Vac (single-phase secondary line+ground wire)

          Frequency

          50/60Hz±10%

          Output

          Voltage

          220/230±1%Vac

          Frequency

          Synchronized with input (mains mode), 50/60Hz±0.5% (battery mode)

          Discharge waveform

          Pure sine wave

          Transfer time

          Zero interruption

          Built-in battery (12V)

          7Ah/9Ah×2


          7Ah/9Ah×4

          -

          7Ah/9Ah×6


          External battery DC voltage nominal


          36Vdc


          72Vdc


          96?Vdc

          Battery type

          Valve-controlled lead-acid maintenance-free storage battery

          Overload capacity

          105% -120%, to?bypass?after?10 seconds;
          120-140%,?to?bypass?after?200ms;
          ? ?140-150%, to?bypass?after?200ms, and then shutdown?10 seconds later;
          ? > 150% shutdown?immediately

          Load peak ratio

          3?:1(?max)

          Distortion rate(full load)

          <3%(linear load)

          <5%(nonlinear load)

          Communication interface

          Rs-232 interface (optional USB interface)+SNMP smart slot

          Working temperature

          0℃~40℃

          relative humidity

          0~90%(no condensation)

          Dimension(D×W×H)

          405×145×220mm

          465×196×345mm

          Net weight (kg)

          10.5/11.4

          6.5

          18.5/20.3

          12

          23.5/26.2

          12.5

          Compliance with standards

          GB/T14715-2017; YD/T1095-2018; EN62040-1:2008+A1:2013; EN62040-2:2018

          Remarks:

          1. Select the rated capacity (output power) PF = 0.8.

          2. The model with "S" is a extended time model, and the battery should be configured according to the external battery DC voltage, and the DC voltage of D 2 KS external battery can be selected as 96 Vdc.

          3. Other internal battery configurations are available in the following models:

          D1K: 12V7Ah/9Ah×3 ; D2K: 12V7Ah/9Ah×6 ; D3K: 12V7Ah/9Ah×8 ;

          4. Load in high altitude = rated power x reduction coefficient

          Altitude (m)

          1000

          1500

          2000

          2500

          3000

          3500

          4000

          4500

          5000

          Frequency reduction coefficient

          100%

          95%

          91%

          86%

          82%

          78%

          74%

          70%

          67%

          * The above parameters may be adjusted and changed, please refer to the physical object. If the UPS is used above 1000m, decreasing rated output must be used, refer to the table above.